|
|
||
| 1 | Operating Principles |
|
| 2 | Construction | |
| 3 | Drive Characteristics | |
| 4 | Timing Characteristics | |
| 5 | Filament Power Supply | |
| 6 | Filament Bias Voltage | |
| 7 | Grid and Anode Power Supply | |
| 8 | Precautions | |
| The contents of this document are subject to copyright and may not be amended
or included in other documents or media without the express permission of Noritake Co., Limited, Japan. Revised 28th July 2001. |
||
| 2. VFD Construction | |
Noritake Itron VFDs have several methods of construction. The basic model is that of the frame type construction. The other variants are specific to the product type and are described in more detail in the relevant application notes associated with CIG (Chip in Glass Driver), Active Matrix and Rib Grid VFDs |
|
![]() |
The Grid Rim,
Filament Support and Lead Pins are provided on a single metal frame. The
ends of the Grid Rim are extended to the outside of the envelope, and are
formed as lead pins for the Grids. The Anode leads are extended into the
envelope to connect with the pads which are placed on the glass substrate.
Both ends of the filament are welded to the Filament Support and Anchor
with the appropriate tension. The Frame is assembled with the Face Glass and Glass Substrate (Anode Plate). The Lead Pins are tinned and formed into a suitable shape for PC Board assembly. FRAME-Types require press formed metal dies for construction. They offer good production yield and high reliability against various environmental conditions. A hybrid of this construction mounts the grids directly on the glass substrate which allows complex grid patterns. |
|
Fig. 3 Frame Type Construction |
|
| 3. VFD Drive Characteristics | |||||
|
|
|||||
|
3.1.1 Static Drive
|
|||||
|
3.1.2 Multiplex Drive (Dynamic Drive)
To minimize the number of pin connections and driver chips, the majority of VFD's use the multiplexing drive method. As shown in Fig.6, corresponding anode segments are connected in common under each separate grid, with each in turn being connected to a data line. Each character has its own separate grid which not only diffuses the electrons from the filaments, but also controls the selection of the character position in a "time share" multiplexing cycle. The duty cycle 'on time' of each character will determine the appropriate operating voltage required to provide sufficient luminance. Fig.7 shows the basic driving circuit. |
|||||
|
Fig.8 Example
Timing Chart of Multiplex Drive VFD |
The timing T1 in Fig.8 shows that when Grid 1 (G1) is ON and data lines Pb and Pc are ON under Grid 1, with all the other grids OFF, the numeric character '1' will be displayed. After the time period T1, Grid 1 is turned OFF and the voltages on the anode data lines are reconfigured to suit the requirements of Grid 2. Grid 2 is then turned ON. In the example, this will be the numeric character '2'. The scanning of Grid 1 to Grid n should be repeated at more than 100 times per second so that persistence of vision in the human eyes gives a stationary, solid display without any flicker. The number of grids and anodes is optimized to reduce the number of lead pins to a minimum. Other factors may be important so the multiplexing drive can be a duplex drive, where the display is separated under two grids, taking advantage of requiring fewer drive chips than static mode and a lower drive voltage than that required by an ordinary multiplexing mode. |
| 4. Timing Characteristics for Correct Operation | ||||||||||
4.1 Grid Scanning Frequency (Refresh Frequency) |
|
|||||||||
| When multiplexing, the selection of a slow grid scanning frequency may cause a flickering effect, which is a result of the optical beat generated by the on and off luminescent cycle and the image retention of the human eyes. As the anode and grid current is varied by the filament voltage level, you may observe flickering when the beat frequency between the AC filament (or pulse) and the grid scanning is 40Hz or less. Therefore we would suggest combinations as per Table 1. |
|
|||||||||
| Alternatively, high frequency scanning may cause problems because of insufficient pulse width for luminance against blanking time. If flickering is caused by this, avoid a scanning frequency between 250Hz and 500Hz. |
||||||||||
| 4.2 Inter-Digit Blanking | ||||||||||
| Another potential
hazard in multiplexing is ghosting. This phenomena is caused by decaying
grid signal pulses which are caused by stray capacitance between VFD
electrodes and display drivers. If the grid timing overlaps the following
grid and anode signal pulses, as shown in Fig.9(a), ghost illumination
appears at un-addressed anode segments. To overcome this problem, an inter-digit blanking time should be added between grid pulse timings as shown in Fig.9(b). Generally the inter-digit blanking time should be approximately 10 to 50usec, but this can vary depending on the delay time. Delay time occurs when high value pull down resistor type drivers are used or when the drive circuit is situated away from the VFD. We recommend that an appropriate inter-digit blanking time is utilized on the grid signal only, rather than on both grid and anode signals. |
|
|||||||||
| 5. Filament Power Supply | |||
5.1 Filament Voltage |
|||
![]() Fig.10 Luminance and Filament Voltage |
Luminance varies with the filament voltage (Ef) as shown in
Fig.10. Since the lifetime of a VFD is dictated by the extent of
evaporation of oxide materials coated onto the tungsten filament wires, it
is critical that the filament voltage is supplied within the specified
ratings.
Current drain from the anodes
and grids to the filaments can cause ghost illumination so a bias voltage
is applied to the filaments to raise them above ground. This is described
later.
|
||
|
5.2 AC Filament Drive (50 or 60Hz) |
|||
|
|
Generally, the transformer is the most
popular device utilized to supply the filament voltage (Ef) with a 60(or
50)Hz sine wave which also has a center-tap for cathode bias as shown in
Fig.11. The center - tap technique is used to prevent luminance slant i.e.
difference in brightness from one side of the display to the
other. Using a transformer without this center-tap can not only cause luminance slant but also ghost illumination due to exceeding the amplitude of the filament voltage in excess of the specified cut-off bias voltage rating. |
||
![]() Fig.12 Transformer without Center-Tap |
|||
| 5.3 Pulse Filament Drive (High Frequency RMS) | |||
|
|
In the case of a DC or battery power supply, a pulse wave form
for the filaments can be generated from a DC to AC converter. The concept
of pulse voltage supply to the filament is the same as AC filament drive.
In either case Noritake still recommends the DC to AC converter with a
center-tap as shown in Fig.13. Please note that the pulse voltage should
be calculated as an RMS (root mean square) value from the wave form as
shown in formula (1). However, a 1/2 duty factor should be set, and the peak to peak pulse wave form should be 1.5 times or less than the RMS value. A frequency range of 10kHz to 200kHz is recommended. |
||
| 5.4 DC Filament Drive | |||
|
|
If a DC filament drive is adopted, a potential difference between the anode and grid voltage will be apparent as a luminance slant across the display as shown in Fig.14. This shows brighter luminance at one side of the display due to the DC voltage drop. In order to avoid this problem, special measures are applied during display construction and the polarity (+,-) of the filament or grid terminal is specified. However, this is only possible for relatively short length VFD's. | ||
| Note : Please consult Noritake in advance before designing DC or DC pulse filament drive circuits. | |||
| 6. Filament Bias Voltage (Cut-off Bias) | ||
6.1 Cut-Off Characteristics (Grid/Anode Cut-off Voltages) |
||
| Luminance (L) varies with the
anode voltage (eb) as shown in Fig.15 when the grid voltage (ec) is a
constant. Luminance also varies with the grid voltage as shown in Fig.16
when the anode voltage is a constant. To completely turn off the
luminescence at the un-addressed display segments, a negative voltage
shall be applied to the un-addressed anodes and grids with respect to the
filament. These negative voltages are called anode cut-off voltage (Ebco)
and grid cut-off voltage (Ecco) respectively. The cut-off voltage-varies
depending on each type of display due to various differences in filament
voltage and wave form. Please note that the cut-off voltage quoted in each
particular specification is based upon the AC voltage being supplied via a
transformer complete with center-tap. |
Fig.15 Anode Voltage and Luminance |
Fig.16 Grid Voltage and Luminance |
| 6.2 Filament Bias Voltages (Ek) | ||
|
|
The filament bias
voltage (Ek) is a voltage applied to the filament center-tap in order to
cut off background illumination when the anodes and grids are not
addressed. The 'off' anode and grid voltages remain negative with respect
to the filament. The total supply voltage Vdisp is ec(eb) + Ek. ( In the
case of CIG displays, the Ek is included in VDD2.) |
|
| In typical driving circuits, a zener diode supplies the Ek as shown in Fig.17. The cathode bias (Ek) for filament center-tap is higher than that specified for the grid cut-off voltage (Ecco). Usually, the Ek is set at the same value as MIN voltage of Ecco shown in the specification or a slightly large value when utilizing a filament center tap (F.C.T.). If a center-tap is not available, a virtual center-tap with resistors is one acceptable alternative. | ||
| 7. Anode and Grid Power Supply | ||
7.1 Circuits As shown in Fig.17, the power supply voltage for anode and grid should be Vdisp = ebc+ Ek (Volts) which is the sum of grid/anode voltages (ebc=ec=eb) and cathode bias voltage (Ek). This output voltage must be stabilized otherwise its ripple may coincide with the grid scanning frequency and may cause flickering of the display. |
||
7.2 Relationship between voltage and brightness A peculiarity of VFD is that both grid and anode are active when high. If there are any limitations with the power supply and/or driving software, the supply voltage or duty factor may not be available to meet the specified value (typical ratings). In this case, you may re-calculate the ratings using the following formula. |
||
|
L = K * ebc^2.5 * Du ....... (2) |
K: constant of each display ebc: anode and grid voltage (ec=eb) Du: Duty factor |
|
| For example, when the duty factor is beneath the specified rating, a specified brightness rating can be achieved by modifying ebc^2.5*Du. If Du(TYP) and ebc(TYP) are as specified, and Du(x) and ebc(x) are modified values than the related expression is as follows: | ||
|
L = K * ebc(TYP)^2.5 * Du(TYP) ...... (3) L = K * ebc(x)^2.5 * Du(x) .............. (4) ebc(TYP)^2.5 / ebc(x)^2.5 = Du(x) / Du(TYP) ......... (5) IMPORTANT
! |
||
7.3 Brightness Control (Dimming) |
||
|
|
High
brightness is the main characteristic of VFD. However, in certain
applications, it may be desirable to offer dimming capabilities for
operation in dark environments. In such a case, the brightness level can
be controlled by reducing the duty factor as shown in Fig.18. The
brightness level can be adjusted in proportion to the luminous 'on' time
to 'off' time. However brightness dimming by reduction of filament voltage
or anode/grid voltage is not recommended because this may cause uneven
illumination. |
|
| The data for electrical
characteristics, reliability and lifetime expectancy has been based on
typical driving conditions. When designing circuitry, apply the typical
rate of driving voltage or, if the voltages fluctuate, the minimum and the
maximum values of the driving voltage should be set within specified
ratings. Exceeding any of the maximum ratings may cause damage to the display, or driving below minimum ratings may cause insufficient brightness. Displays used under anything other than specified conditions will be defined as out of warranty. |